Mandatory requirement for commercial kitchens

 

Ventilation interlock system has been designed to use in

commercial kitchens to meet BS6173:2001

 If extract or supply fan is switched off when mains are applied to the unit (fan off) indicator will illuminate and no gas flow will be available to the burners. When fans are switched on (fan off) indicator will extinguish and gas flow will be available to the burners 

In the event of fan failure (either fan) Fan Off indicator will illuminate and gas will be shut off to the burners. When fault on fan has been rectified and fan switched on (Fan Off) indicator will extinguish and gas flow will be restored. The same sequence of events will occur in the event of an air flow switch fault or extractor filter is blocked

 There is a remote On/Off facility available which can be operated by either a manual remote switch or volt free contact; however gas cannot be switched on if no air extraction is present 